Technical Memoranda TM 1/90 Air conditioning condenser cooling systems: cost considerations
Publication Year
1990
Document Status
Withdrawn
Abstract
Presents an updated version of a study carried out by BSRIA in 1987 of the relative costs of alternative wet and dry condenser cooling systems serving the chillers of an air conditioned office building. Since then, more specific water treatment and maintenance requirements for cooling towers have been published to minimise the risk of an outbreak of Legionnaires' disease, and this has modified the cost assessment. Revises the original case study capital and running costs to late 1989 prices and assesses the current water treatment and maintenance costs. States that the revised assessment of overall costs shows that up to a cooling load capacity of 1,200kW the packaged air cooled chiller option is cheaper than a cooling tower or dry cooler system with separate chillers. The cooling tower system however requires the least roof space.
ISBN
9780860222569
Publisher Information
BSRIA Limited
BSRIA was founded in 1956. It is a consultancy, test and research organisation which publishes technical notes and guidance for designers and specifiers of building services.
Old Bracknell Lane West
Bracknell
Berkshire
BSRIA
UK
Website: https://www.bsria.com/uk/
Email: bsria@bsria.co.uk